E.9 Network operator questionnaire


A completed E.9 sheet contains information that is necessary for the EZA controller and the telecontrol system. All relevant sections are listed below.


Page 1:

  • System name
  • Agreed connection active power for feed-in PAV,E: Active power of the customer system agreed between the grid operator and the connec
    feed-in at the grid connection point. Should normally correspond to the sum of the maximum AC active power of the inverters. Is used as a reference value for Q(P) characteristic curve, whereby 1.0 Pmom/Pb inst is equal to PAV,E.
  • Reference system present: must be taken into account when configuring the reactive power control if necessary (see table on page 5 below)

Page 5:

  • Static voltage maintenance:
    • Reactive power setting range: maximum or minimum reactive power that the system must be able to generate
    • Reactive power setpoint and method: Reactive power method (in accordance with VDE-AR-N 4110/4120), which must be configured in the digital twin.
    • All settings below the displacement factor cos φ must currently still be set by Amperecloud. 
    • Mixed systems: if the points are set at different locations, 2 grid analysis devices must be installed (NAP and EZE)

Page 6:

  • Agreed supply voltage of the network UC: Reference voltage when using the Q(U) characteristic curve

Need More Help?

If you encountered any difficulties or need further assistance, here are some steps you can take:

Contact Support:

  • Email: Reach out to our support team by emailing us at support@amperecloud.com. Provide as much detail as possible about the issue you're facing.

Phone Support:

  • Call our customer service at

    +49 30 6293 77201. Our support hours are Monday to Friday, 9 AM to 5 PM (local time).


Share Your Feedback

If this article didn’t meet your needs or if you have suggestions on how we can improve, please let us know by submitting feedback. Your input helps us enhance our resources and support.